HPQ-135G-Compact Filters-BEIJING AIHE NUCLEAR POWER TECHNOLOGY CO.,LTD.




    WELCOME TO BEIJING AIHE NUCLEAR POWER TECHNOLOGY CO.,LTD.!

    • 中文版
    • English

    SPECIFICATIONS

    Application: HVAC, Industry

    Frame: Galvanized steel

    Spacers: Hotmelt

    Bonding: 2 component polyurethane

    Media: Glass fibre paper

    Gasket: Continuous poured gasket

    Filter class according to EN779:2012: M6, F7

    Maximum / recommended final pressure drop: 450Pa

    Maximum temperature: 65°C

    Maximum relative humidity: 90% 

    Comments: It is preferredd to use a pre filter with these products


    ADVANTAGES

    • Small constructionspace

    • Low pressure drop


    DETAIL

    Qualities

    AFPRO compact filters or HPQ – High Performance Quality –filters are mini-pleated filters, 

    characterised by their high filtration characteristics. The glass fibre filter medium is 

    made with a “wet-laid paper technique” that guarantees high dust retention effectiveness 

    and constant filter efficiency. The technology guarantees sustainability,which is expressed 

    as reduced air resistance and lower energy consumption. The compact filters gain an A energy 

    label time and again for this very reason!


    Advantages of compact filters (HPQ filters)

    • Large filter area

    • Spacers – hot melt

    • 100% leak free

    • Very great dust retention capacity

    • Long lifetime

    • Low energy consumption

    • Dimensioning according to EN15805

    • Moisture resistant

    • Corrosion free

    • Fully combustible


    Structure

    Compact or HPQ filters are mini-pleated filters that are assembled in a polystyrene frame. 

    This type of air filter can withstand temperatures up to 70°C. The largely robot-automated 

    production of these filters ensures that they comply with the highest quality standards.


    Application

    Compact or HPQ filters are used in air conditioning units and systems,

    industrial systems and as pre-filters for clean rooms.


    Installation

    • Ensure that the filter is correctly installed:suction side – clean air side

    • Filter must be correctly mounted: no leaks

    • Gaskets must not be damaged

    • Filter must be clamped down in four places

    • Avoid touching the filter medium during installation

    • Avoid damaging the filter during installation

    • System must run for a few hours to achieve the desired result

    • Installation record for filters: note date, time, initial resistance




    BACK